Condenser Water Flow Calculator

Condenser-side flow from load and ΔT, including the compressor heat of rejection.

0
Heat of rejection (kW)
0
Condenser flow (L/s)

The tower must reject the load PLUS the compressor work — that's why condenser flow runs ~25% above evaporator flow at the same ΔT.

Formula

Q_rej = Q_evap + P_compressor; flow = Q_rej/(c_p·ΔT)
References: AHRI 550/590; tower selection practice

Condenser Water Flow Calculator is a free condenser water flow for HVAC designers, technicians and energy auditors — instant, accurate and 100% client-side, with the governing formula and reference shown next to the result so the number can be defended, not just quoted.

About Condenser Water Flow Calculator

Condenser-side flow from load and ΔT, including the compressor heat of rejection. The calculation implements Q_rej = Q_evap + P_compressor; flow = Q_rej/(c_p·ΔT) (AHRI 550/590; tower selection practice). The tower must reject the load PLUS the compressor work — that's why condenser flow runs ~25% above evaporator flow at the same ΔT.

How to use Condenser Water Flow Calculator

  1. 1Enter Evaporator load in TR.
  2. 2Enter Chiller efficiency in kW/TR.
  3. 3Enter Condenser ΔT in °C.
  4. 4Read Heat of rejection, Condenser flow instantly — no submit button needed.
  5. 5Need US units? Flip the SI/Imperial toggle and every field converts.

Why use Condenser Water Flow Calculator?

  • Implements the standard formula — Q_rej = Q_evap + P_compressor; flow = Q_rej/(c_p·ΔT)
  • Reference cited on-page: AHRI 550/590; tower selection practice
  • One-click SI ⇄ Imperial toggle — values convert in place, physics stays in SI
  • Live worked example: the substitution recomputes from your numbers
  • Runs entirely in your browser — nothing uploaded, free forever

Frequently asked questions

What formula does the Condenser Water Flow Calculator use?+

It computes Q_rej = Q_evap + P_compressor; flow = Q_rej/(c_p·ΔT), per AHRI 550/590; tower selection practice. The formula is displayed under the result along with a worked example substituted with your own inputs.

What should I keep in mind when using this calculator?+

The tower must reject the load PLUS the compressor work — that's why condenser flow runs ~25% above evaporator flow at the same ΔT.

Is this based on ASHRAE methods?+

The calculations follow the standard ASHRAE/ISHRAE formulations cited under the result, simplified where industry practice does the same. For permit-grade design, confirm with the full code procedure.

Is the Condenser Water Flow Calculator free to use?+

Yes — completely free, no sign-up, no limits. It runs client-side in your browser, so inputs stay private and results are instant even on slow connections.