Humidifier Sizing Calculator

Moisture load (kg/h) to hold an indoor RH target against ventilation in winter.

0
Humidification load (kg/h)
0
If isothermal (steam): power (kW)

Ventilation dominates winter humidification โ€” every L/s of cold outdoor air needs continuous water. Watch window condensation before chasing 50% RH.

Formula

แน_w = ฯยทVฬ‡ยท(w_in โˆ’ w_out); steam power โ‰ˆ 0.75 kW per kg/h
References: ASHRAE Handbook โ€” Systems, humidifiers chapter

Humidifier Sizing Calculator is a free humidifier size for HVAC designers, technicians and energy auditors โ€” instant, accurate and 100% client-side, with the governing formula and reference shown next to the result so the number can be defended, not just quoted.

About Humidifier Sizing Calculator

Moisture load (kg/h) to hold an indoor RH target against ventilation in winter. The calculation implements แน_w = ฯยทVฬ‡ยท(w_in โˆ’ w_out); steam power โ‰ˆ 0.75 kW per kg/h (ASHRAE Handbook โ€” Systems, humidifiers chapter). Ventilation dominates winter humidification โ€” every L/s of cold outdoor air needs continuous water. Watch window condensation before chasing 50% RH.

How to use Humidifier Sizing Calculator

  1. 1Enter Ventilation airflow in L/s.
  2. 2Enter Target indoor humidity ratio in g/kg (22 ยฐC/45%RH โ‰ˆ 7.4 g/kg).
  3. 3Enter Outdoor humidity ratio in g/kg (0 ยฐC/80%RH โ‰ˆ 3; โˆ’10 ยฐC โ‰ˆ 1.3).
  4. 4Read Humidification load, If isothermal (steam): power instantly โ€” no submit button needed.
  5. 5Need US units? Flip the SI/Imperial toggle and every field converts.

Why use Humidifier Sizing Calculator?

  • โœ“Implements the standard formula โ€” แน_w = ฯยทVฬ‡ยท(w_in โˆ’ w_out); steam power โ‰ˆ 0.75 kW per kg/h
  • โœ“Reference cited on-page: ASHRAE Handbook โ€” Systems, humidifiers chapter
  • โœ“One-click SI โ‡„ Imperial toggle โ€” values convert in place, physics stays in SI
  • โœ“Runs entirely in your browser โ€” nothing uploaded, free forever

Frequently asked questions

What formula does the Humidifier Sizing Calculator use?+

It computes แน_w = ฯยทVฬ‡ยท(w_in โˆ’ w_out); steam power โ‰ˆ 0.75 kW per kg/h, per ASHRAE Handbook โ€” Systems, humidifiers chapter. The formula is displayed under the result.

What should I keep in mind when using this calculator?+

Ventilation dominates winter humidification โ€” every L/s of cold outdoor air needs continuous water. Watch window condensation before chasing 50% RH.

Is this based on ASHRAE methods?+

The calculations follow the standard ASHRAE/ISHRAE formulations cited under the result, simplified where industry practice does the same. For permit-grade design, confirm with the full code procedure.

Is the Humidifier Sizing Calculator free to use?+

Yes โ€” completely free, no sign-up, no limits. It runs client-side in your browser, so inputs stay private and results are instant even on slow connections.